IEC 60309

Print-Friendly
About 2 pages (507 words)

Bookmark and Share Know this topic well? Help others and get FREE products!

IEC 309 (now IEC 60309, 1999) is an international standard from the International Electrotechnical Commission for "plugs, socket-outlets and couplers for industrial purposes". Part 1 of the standard specifies general functional and safety requirements for any form of industrial high-current power connector. Part 2 specifies a range of mains power connectors with circular housings, and different numbers and arrangements of pins for different applications. The highest voltage allowed in the standard is 690 volts DC or AC, the highest current 250 amperes, and the highest frequency 500 hertz. The temperature range is −25 °C to +40 °C. In the United Kingdom, this standard was first adopted as BS 4343:1968 and has since been replaced by its Europe-wide equivalent BS EN 60309:1999.

Keying

16 A 3P+E 400 V plug
16 A 3P+E 400 V plug
16 A P+N+E 230 V plug
16 A P+N+E 230 V plug
Mated 16 A plug and wall-mounted socket
Mated 16 A plug and wall-mounted socket

IEC 60309-2 connectors are produced in many variants, designed so that a plug of one type can only be inserted into a socket of the same type. Different current ratings (such as 16 A, 32 A and 63 A) are distinguished by different diameters of the circular housing. Different voltage and frequency combinations are distinguished by the location of the ground pin (or a plastic projection called the minor keyway, for connectors with no ground pin), as shown in the following table. The ground pin can be in one of twelve locations spaced at 30° intervals around the circle on which all the pins lie. Position 6 is at the same angle as the major keyway, a projection on the plug casing that aligns with a notch on the socket. The ground pin has a larger diameter than the other pins, preventing the wrong type of plug being inserted in a socket.

Number of pins
P+N+E 3P+E 3P+N+E
Ground
pin
location
2 >50 V, 300-500 Hz, green housing >50 V, 300-500 Hz, green housing >50 V, 300-500 Hz, green housing
3 50-250 V AC 380 V, 50 Hz
440 V, 60 Hz
220/380 V, 50 Hz
250/440 V, 60 Hz
4 100-130 V AC, yellow housing 100-130 V AC, yellow housing 57/100 - 75/130 V AC, yellow housing
5 277 V, 60 Hz 600-690 V AC, black housing 347/600 - 400/690 V AC, black housing
6 200-250 V AC, blue housing 380-415V AC, red housing 200/346 - 240/415 V AC, red housing
7 480-500 V AC, black housing 480-500 V AC, black housing 277/480 V - 288/500 V AC, black housing
8 250 V DC - -
9 380-415 V AC, red housing 200-250 V AC, blue housing 120/208 V - 144/250 V AC, blue housing
10 - >50 V, 100-300 Hz, green housing -
11 - 440-460 V, 60 Hz, red housing 250/440 V - 265/460 V, 60 Hz, red housing
12 - - -

A six-phase plus earth (6P+E) version also exists.

See also

External links

http://www.globetron.com/GlobetronPowerConnectors.pdf#page=1

View More Summaries on IEC 60309
 
Ask any question on IEC 60309 and get it answered FAST!
Answer questions in BookRags Q&A and earn points toward
discounted or even FREE Study Guides and other BookRags products!
Learn more about BookRags Q&A
Copyrights
IEC 60309 from Wíkipedia. ©2006 by Wíkipedia. Licensed under the GNU Free Documentation License. View a list of authors or edit this article.

Article Navigation
Join BookRagslearn moreJoin BookRags




About BookRags | Customer Service | Report an Error | Terms of Use | Privacy Policy